New Zealand's wiring rules moved from AS/NZS 3000:2007 to AS/NZS 3000:2018 (with Amendments 1 to 3) on 13 November 2025, under the Electricity (Safety) Amendment Regulations 2025 (SL 2025/225). The 2007 edition was accepted only until the close of 12 November 2026. From 13 November 2026, new work must be done to the 2018 edition, except a job already under construction before 13 November 2025. Existing installations never need upgrading just because the edition changed.

If you are still wiring to the 2007 wiring rules out of habit, that habit stopped working for new work at the close of 12 November 2026. eCertify inspects mains work and parallel generation for other electricians across Auckland, and the edition question is the first thing that trips a job up before anyone looks at a single conductor.
Direct answer: New Zealand's wiring rules moved from AS/NZS 3000:2007 to AS/NZS 3000:2018 (with Amendments 1 to 3) on 13 November 2025, under the Electricity (Safety) Amendment Regulations 2025 (SL 2025/225). Under the transition rules in Schedule 1AA of the Electricity (Safety) Regulations 2010, work done to the 2007 edition was treated as complying only until the close of 12 November 2026. From 13 November 2026, new work must be done to the 2018 edition; the one exception is a job already under construction before 13 November 2025, which can still be finished to 2007. Existing installations never need upgrading just because the edition changed.
Have mains or solar work that needs inspecting? Book a Record of Inspection with eCertify, or call 09 302 0884.
AS/NZS 3000 is the Wiring Rules: the technical standard the Electricity (Safety) Regulations 2010 ("ESR") point to for how an electrical installation must be designed, built and tested. The ESR does not print the Wiring Rules itself; it cites a specific edition, and that citation is what has legal force. For years New Zealand kept citing the 2007 edition (with Amendments 1 and 2) even after Australia had already moved on. That citation has now changed, and it changes what a current CoC (Certificate of Compliance) has to be checked against.
The Electricity (Safety) Amendment Regulations 2025 (SL 2025/225) updated the Electricity (Safety) Regulations 2010, Schedule 2, moving the cited standard to AS/NZS 3000:2018, which carries Amendments 1, 2 and 3. This took effect on 13 November 2025. Eleven New Zealand modifications were added at the same time, two of which (RCD testing and RCD types) are covered in their own post below. The standard itself has not been reissued since 2018; "AS/NZS 3000:2023" or "the 2025 Wiring Rules" are not real editions, whatever you have seen written elsewhere.
AS/NZS 3000:2018 prints an asterisk in the margin beside each clause, table or figure it changed significantly from the 2007 edition, and Amendments 1 to 3 flag their own edits with a bar and a tag. eCertify read all 395 marked items against the 2007 edition, or against the amendment itself, and has written up the 295 that change something of substance, each in one plain sentence. Marked items whose change is only editorial, such as a corrected cross-reference or a renumbered rule, are left off, and each page says how many it left off and why. The clause numbers and headings are the standard's and the sentences are eCertify's, so check the standard itself before you rely on a detail on site.
Schedule 1AA of the Electricity (Safety) Regulations 2010 treated you as complying until the close of 12 November 2026 if the work met whichever official standard applied immediately before 13 November 2025, which in practice meant the 2007 edition. That fallback was tied to the date, not to when a job started, and it ended at the close of 12 November 2026. From 13 November 2026, 2018 is the only edition that counts for new work.
In practice, this is what the transition rule means for a job:
A CoC for any job that started before 13 November 2026 should say plainly which edition each stage of the work was done to. That is not a cosmetic note: eCertify checks the stated edition against the dates on the job before relying on it.
No. Schedule 1AA of the Electricity (Safety) Regulations 2010 lets any installation, fitting or appliance that already complied with the rules in force immediately before 13 November 2025 keep being built, installed, sold, used and maintained under those same rules, provided it is not electrically unsafe. The same clause lets it be tested, certified or inspected under those rules too. Nothing about the 2018 edition forces a rewire, a switchboard replacement or a new RCD on a property just because the standard moved.
This is eCertify's own working rule on an inspection: a 2007-compliant installation is not a defect for failing to meet 2018. An inspector flags what is actually unsafe or non-compliant with the standard it was built to, not a gap between two editions that the regulations themselves say is acceptable.
Two differences between the editions are doing almost all of the damage in practice, each with enough depth to need its own post:
Clause 2.3.2.1.2(b) and (c) of AS/NZS 3000 bans a switch or circuit-breaker in the neutral of consumer mains, and bans switching a combined protective-earth-and-neutral (PEN) conductor or an earthing conductor. New Zealand disapplied that ban from 13 November 2025 on WorkSafe's recommendation, which WorkSafe has said was groundwork for EV charger protection devices and island-mode backup. The Electricity (Safety) Amendment Regulations 2026 (SL 2026/309) revoked that disapplication from 2 October 2026, so the ban is back in force, unmodified, for any new work from that date; MBIE pointed to "significant concern within the sector" about safety, after inspectors and engineers warned that opening the PEN can make earthed metalwork live with no fault present. Anything installed or under way before 2 October 2026 does not have to be undone, but only if it is not electrically unsafe and complied with the rules in force at the time, so a PEN switch found on site still needs assessing. This is covered in full, with what it means for a changeover switch already on site, in eCertify's AFDD and PEN switching post.
If your house was wired under the old rules, it does not need upgrading because the standard changed. Your installation can be repaired, maintained and inspected under the rules it was built to, as long as it is safe. The edition only matters if you are having new work done: from 13 November 2026 any new work must be done to the 2018 edition. If an insurer, buyer or your bank is asking for a certificate, eCertify's certification page sets out which document you actually need and what it costs, and our FAQ answers the most common certificate questions.
New Zealand moved the cited edition of the Wiring Rules from AS/NZS 3000:2007 to AS/NZS 3000:2018 on 13 November 2025, and 2007 stopped being a lawful fallback for new work at the close of 12 November 2026. eCertify, Auckland's electrical compliance specialist, treats a 2007-compliant installation as compliant, not defective, because that is what the Electricity (Safety) Regulations 2010 themselves say. The two changes worth knowing in detail, instrument RCD testing and mandatory AFDDs in specific locations, each get their own post, and the short-lived change to PEN switching rules is back to the pre-2025 position from 2 October 2026. If you are certifying mains work or parallel generation, eCertify's write-up of high-risk electrical work and mains inspections explains the inspection and Record of Inspection that high-risk work needs.
Need high-risk work inspected? See eCertify's Record of Inspection page for Auckland electricians for prices and booking, or call 09 302 0884.
The Electricity (Safety) Regulations 2010 is the regulation that sets New Zealand's electrical safety rules and cites the Wiring Rules edition that applies. It is the instrument SL 2025/225 and SL 2026/309 both amend.
No. The current cited edition is AS/NZS 3000:2018 with Amendments 1 to 3. No new edition has been published since 2018.
Yes. New Zealand modifies the printed standard with its own clauses in Schedule 2 of the Electricity (Safety) Regulations 2010, covering items such as RCD testing, RCD types and PEN switching.
AS/NZS 3000:2018, incorporating Amendments 1, 2 and 3, cited from 13 November 2025.
Because the standard a CoC is checked against depends on the dates of the work. Work done to the 2007 edition was only treated as complying until the close of 12 November 2026, unless the job was already under construction before 13 November 2025, so getting the edition wrong on a CoC is an easy, avoidable mistake.