AS/NZS 3000:2018 appendix changes: what is new or revised

The appendices of AS/NZS 3000:2018: eCertify lists 26 of 32 marked changes since 2007, plus two added by hand, and explains each in one plain sentence.

Electrical Certificate of Compliance form on a clipboard with blank fields

This page is part of eCertify's guide to what changed from AS/NZS 3000:2007 to 2018. It covers the appendices at the back of the standard: referenced documents, the circuit protection guide, maximum demand, building codes, surge protection, IP ratings and symbols, and the new appendices on switchboards, power outages, conduits, arc fault detection devices, EV charging and d.c. circuits.

AS/NZS 3000:2018 marks 32 appendix items as changed. This page lists 26 of 32 marked changes, plus two the standard left unmarked; the other six are editorial only (a placeholder for deleted text, corrected table numbers and a load group letter, a moved paragraph and two index fixes). eCertify read every one against the 2007 edition or the amendment itself. The substance is in maximum demand, where EV charging and a switchboard diversity method arrive, and in six new appendices. Every appendix is guidance, not a rule, and New Zealand modifies none of them.

Appendix changes in plain words

eCertify's short version of what the appendices now give you on the job:

  • Table B1 route lengths are unchanged, but they cover fault protection only, so check voltage drop and overload separately. (Table B1, Table B2)
  • Count EV charging in maximum demand: the domestic, non-domestic and energy demand tables each gain an EV line. (Tables C1, C2, C3)
  • For a board built to AS/NZS 61439, you can now work out maximum demand from circuit ratings and a diversity factor. (C2.4.4, Table C4)
  • In New Zealand, Appendix E now names the Electrical Safety Certificate (ESC), not the Certificate of Compliance (COC), as what consent authorities accept. (E3.2, E3.3)
  • Fit surge protection devices after the main switch and ahead of any RCD, on short leads of at least 6 mm². (F1.2.2, Appendix F)
  • Enclosed PV switch disconnectors call for IP56NW, which means no water at all gets in during the IPX6 water test. (Appendix G)
  • New guidance appendices cover AS/NZS 61439 switchboards, outage planning for home medical users, conduit markings, EV charging and d.c. circuits. (K, M, N, P, Q)
  • Appendix O gives guidance on arc fault detection devices (AFDDs) for when an owner chooses to fit them, though it carries no margin mark. (Appendix O)
  • Appendix E's new building classes come from Australia's construction code and do not apply in New Zealand. (E2.2 to E2.2.4)

How eCertify read the appendix changes

The 2018 edition prints an asterisk in the margin wherever it changed a clause, table or figure significantly from 2007, and Amendments 1 to 3 mark their own edits with a tagged bar. A mark says that something changed, not what. So eCertify set each marked appendix item beside the 2007 edition, checked each amendment-only item against the amendment's own instructions, and put the difference into one plain sentence. Unmarked edits are not listed, with two exceptions the standard's own preface names, and nor are marked edits that are editorial only.

The appendix and clause numbers and the short headings are the standard's. The sentences are eCertify's, so check the standard itself before you rely on a detail on site.

New Zealand check: the Electricity (Safety) Regulations 2010 modify the Wiring Rules for New Zealand in their Schedule 2, and none of those modifications touches an appendix; the October 2026 amendment to that schedule changed a Section 2 clause only. Every appendix on this page is informative, which the standard defines as information or guidance only. Appendix E is the one that splits by country: its E2 part describes Australia's National Construction Code and its E3 part the New Zealand Building Code. Under Schedule 1AA of the same regulations, complying with the 2007 edition stopped counting as compliance at the close of 12 November 2026.

Jordan Statham, eCertify's director, is an EWRB-registered electrical inspector. Appendix E is where the Wiring Rules meet New Zealand's building consent process, and eCertify's page on Energy Works Certificates explains the family of certificates that councils and insurers ask for: the ESC, the COC, the Record of Inspection (ROI) and the Certificate of Verification (CoV).

Referenced documents and the circuit protection guide

eCertify found five changes of substance in Appendices A and B, all of them from Amendment 1 or later. The 2018 edition had already merged 2007's separate normative and informative reference lists into one, as its preface says. The loop impedance testing these route lengths feed into is covered in Section 8, verification and testing.

Appendix A, Referenced documents. The three amendments kept the list current: in came the battery systems standard AS/NZS 5139, IEC 62955 for the d.c. leakage device used in mode 3 EV charging, and the specifications for portable outlet devices, socket-outlet adaptors and cord extension sets, while the 60884 plug and socket-outlet entry, two AS 60269 fuse parts and IEC TR 62432 went out.

Clause B5.2.3, Guidance tables. Amendment 1 rewrote this paragraph so that it introduces Table B2 and the Table C8 voltage drop method alongside the Table B1 route lengths, where 2007 described Table B1 alone.

Table B1, Maximum route lengths. Amendment 1 replaced the table, but every route length matches 2007; what is new is a note that the lengths satisfy fault protection only, leaving overload, short circuit and voltage drop to be checked on their own, and fuses are now referenced to IEC 60269-1.

Clause B5.2.5, Guidance table. New from Amendment 1: a short paragraph on reading Table B2, where bold figures show voltage drop setting the limit and italics show loop impedance setting it.

Table B2, Route length by loop impedance and voltage drop. New from Amendment 1: a side-by-side of the longest single-phase circuit that earth fault-loop impedance allows (Type C breakers, 0.4 s disconnection) and the longest that several voltage drop limits allow.

Maximum demand

eCertify counts five changes of substance in Appendix C, with two themes: electric vehicle charging now has a place in every demand method, and switchboards built to AS/NZS 61439 get a diversity method of their own. Tables were renumbered along the way, so 2007's voltage drop Table C7 is now Table C8.

Table C1, Maximum demand, domestic installations. As the table stands after Amendment 1, which replaced its last six rows, the loads not tied to one living unit are labelled communal, and a new row covers EV charging equipment, which the 2007 table did not have.

Table C2, Maximum demand, non-domestic installations. A new line in the appliance group covers charging equipment for electric vehicles, which the 2007 table did not list.

Table C3, Energy demand method, non-domestic. Open-air and basement carparks each gain an EV charging line, and a new note says EV charging is added on top of every other energy demand.

Clause C2.4.4, Alternative method using switchboard diversity. New in 2018 (2007's C2.4.4 was the worked energy demand example, now C2.4.3.2): for a switchboard built to the AS/NZS 61439 series, maximum demand may be taken as the sum of the circuit overload ratings times a diversity factor from Table C4, in wording Amendment 3 rewrote.

Table C4, Upstream circuit loading after diversity. New in 2018: the diversity factors for that method, which fall as the number of protective devices downstream rises.

Building classes in Australia's construction code (Australia only)

eCertify found six marked items in Appendix E's Australian part, E2, which describes the National Construction Code. None of them applies in New Zealand, where the New Zealand Building Code in E3 is the reference. For the standard's own scope, see Section 1, scope and definitions.

Clause E2.2, Principles of classification. Australia only: a new block, not in 2007, on how the National Construction Code sorts buildings into classes, set out in E2.2.1 to E2.2.4.

Clause E2.2.1, General. Australia only: a building's class follows the purpose it is designed, built or adapted for.

Clause E2.2.2, Classifications. Australia only: the classes themselves, taken from the 2016 code, from Class 1 houses through to Class 10 non-habitable structures such as garages, sheds and pools.

Clause E2.2.3, Multiple classification. Australia only: each part of a building is classed separately, with a rule for a small area used for a different purpose.

Clause E2.2.4, Parts with more than one classification. Australia only: a building or part of one may carry more than one class at once and then has to meet the provisions for each.

Clause E2.3.4, Sustainability, energy efficiency. Australia only: the energy efficiency list now reaches electric resistance heating in commercial as well as residential premises, and limits only the unnecessary running of pool pumps and air systems.

The New Zealand Building Code

eCertify's read of the two New Zealand items in Appendix E: the certificate the appendix now names is the Electrical Safety Certificate (ESC), where 2007 named the Certificate of Compliance (COC).

Clause E3.2, Extent of electrical installations in the NZBC. The list of Building Code clauses that touch electrical work gains F8 signs, uses F6's current name (visibility in escape routes), points G9 to AS/NZS 3000 instead of the 1997 regulations, and adds notes on the ESC and the COC.

Clause E3.3, Building consents. The three cases that need a building consent carry over, but the document the appendix says building consent authorities have to accept as showing the electrical work complies is now the ESC, not the COC.

Surge protection, IP ratings and symbols

eCertify found one marked change in each of Appendices F, G and J. IP ratings are put to work for equipment in Section 4, electrical equipment, and for wet areas in Section 6, bathrooms, pools and spas.

Paragraph F1.2.2, Installation. Amendment 2 rewrote item (a): a surge protection device (SPD) goes after the main switch and ahead of any RCD, the 2007 option of fitting it after an isolation switch is gone, and the pointer for an RCD main switch now sits in the item itself.

Appendix G, Degrees of protection of enclosed equipment. A new paragraph explains the IP56NW rating that AS/NZS 5033 calls for on enclosed PV switch disconnectors, tested like IPX6 but with no water allowed in.

Appendix J, Symbols used in this standard. The symbols summary is now a figure pairing each symbol with its meaning, and it no longer gives each symbol's source in the AS 1102 series as 2007's table did.

New appendices: switchboards, outages, conduits, EV charging and d.c.

eCertify counts five new appendices marked in the margin, all of them guidance. The rules they support sit in Section 2, protection and switchboards, and Section 7, solar, EV and special installations, which holds the New Zealand-only EV charging clause.

Appendix K, Switchboard requirement summary. New, in the slot 2007 left as a deleted appendix: a checklist of what the AS/NZS 61439 switchboard series asks for, covering the run-down of AS/NZS 3439, boards operated by ordinary persons, device substitution, repairs to existing boards and the maker's routine verification.

Appendix M, Reducing the impact of power supply outages. New, replacing 2007's New Zealand electric shock first aid chart (its Australian twin, Appendix L, is now an empty page): steps for homes with assisted-living technology or home medical equipment, from enrolling for priority restoration to full discrimination and a generator connection.

Appendix N, Electrical conduits. New: a guide to the two conduit families on the market, AS/NZS 2053 and AS/NZS 61386, and what their markings and classification numbers mean.

Appendix P, EV socket-outlets and charging stations. New: guidance on EV supply circuits, covering charging modes 1 to 4, an RCD of at least Type A for every connecting point, d.c. fault protection, charging station design and checks on public chargers.

Appendix Q, D.C. circuit protection guide. New: how to choose protection and switching devices for a d.c. supply, covering arc suppression, polarised and non-polarised switchgear, d.c. ratings, isolation, wiring and inverters.

Two changes added by hand

eCertify added two items the margin marks miss, because the standard's own preface lists them as changes and a side-by-side read with 2007 confirms them. They are not counted in the 32. For how AFDDs fit New Zealand work, see eCertify's guide to AFDDs and PEN switching.

Appendix O, Installation of arc fault detection devices. New and unmarked: guidance for where an owner chooses to fit AFDDs, placing each one after the main switch at the origin of the circuit it protects and selecting it to IEC 62606.

Appendix F, Surge protection devices (unmarked update). Unmarked, though the preface names it: fitting structural lightning protection now brings at least a primary SPD, the SPD's backup fuse or breaker sits within the maker's maximum and below the device upstream, and its leads are kept short, direct and at least 6 mm².

In short

In the appendices of AS/NZS 3000:2018, 26 of 32 marked changes are changes of substance, and eCertify adds two the margin leaves out. Comparing them with 2007, eCertify finds the weight in maximum demand, where EV charging and switchboard diversity arrive, in the New Zealand building code notes, which now name the ESC, and in six new guidance appendices. Seven of the 26 are amendment edits only, and New Zealand modifies none of them.