AS/NZS 3000:2018 Section 6 changes: bathrooms, pools and spas

eCertify lists 23 of 36 marked changes in Section 6 of AS/NZS 3000:2018, covering bathrooms, pools, spas and fountains, each in one plain sentence.

Hands lifting the cover of a grey enclosure fixed to an outdoor block wall, cables inside

eCertify's guide to what changed from AS/NZS 3000:2007 to 2018 runs one page per section, and this one covers Section 6, which the standard calls Damp situations: baths, showers and sinks, swimming pools and spa pools, fountains and water features, saunas, refrigeration rooms and areas that are hosed down or sanitised.

AS/NZS 3000:2018 marks 36 items in Section 6 as changed. Thirteen are editorial (single connecting words, corrected cross-references, a reworded scope line, and clauses split into parts with the same requirements), so this page lists 23 of 36 marked changes. Each was checked by eCertify against the 2007 text or, for an amendment edit, the amendment itself. The substance is in shower and sink zones, spa sizes, communal bathroom IP ratings, Zone 0 lights, and two new bans inside the zones, and none is changed for New Zealand.

Section 6 changes in plain words

In eCertify's words, here is what Section 6 now changes for you in wet areas:

  • Treat a deluge shower as a shower and an eyewash station as a fixed water container: that is now a rule, not an option. (6.2.1)
  • For a ceiling shower rose, measure Zone 1 out 1.2 m horizontally, and a barrier of at least 1.8 m can shrink it. (6.2.2.1, Figures 6.5, 6.6, 6.11)
  • A sink or basin bowl over 40 L, not 45 L as before, now takes the bigger Zone 2. (6.2.2.2, Figures 6.13, 6.14)
  • Communal showers no longer step up to IPX5, so IPX4 in Zones 1 and 2 now covers every bath and shower. (6.2.4.1, Table 6.1)
  • Spa pools and tubs up to 680 L, up from 500 L, now follow the bathroom rules. (6.3.2.2.1)
  • Keep generator sets, stand-alone systems, grid-connected inverters and batteries out of every bathroom, pool and fountain zone. (6.2.4.7, 6.3.4.7, 6.4.4.7)
  • Never site a pool, spa or fountain so that a distributor's pit or cabinet lands inside one of its zones. (6.3.4.8, 6.4.4.8)
  • Zone 0 lights in pools and fountains must meet AS/NZS 60598.1 and 60598.2.18 and run on SELV only, unearthed. (6.3.4.5.2, 6.4.4.5.2)
  • Also: a hinged-door shower gets its own zone drawing, the bath and pool tables drop "guidance", and fountains get a table. (Figure 6.8, Tables 6.1 to 6.3)

How eCertify read the Section 6 changes

The 2018 edition puts an asterisk in the margin beside each clause, table or figure it changed significantly from 2007, and Amendments 1 to 3 mark their own edits with a tagged bar. Neither mark says what the change was. eCertify worked through every marked Section 6 item against the 2007 wording, followed the amendment's edit instructions for each amendment-only item, and wrote the difference up as one plain sentence. Edits the standard did not mark are not on this page, and marked edits that only fix wording or numbering are counted but left off.

Clause numbers and headings come from the standard. The sentences are eCertify's own, so open the standard before you lean on any detail on site.

New Zealand check: Schedule 2 of the Electricity (Safety) Regulations 2010 changes some Wiring Rules clauses for New Zealand, and no Section 6 clause is among them; the schedule's October 2026 amendment touched only a Section 2 change. None of the 36 items applies in Australia only, although clause 6.2.2.1 keeps separate Australian and New Zealand figures inside it, and this page gives the New Zealand ones. Schedule 1AA of those regulations closed the general 2007 fallback at the end of 12 November 2026.

eCertify's director, Jordan Statham, holds EWRB registration as an electrical inspector. For homeowners, the eCertify team's visual home electrical safety check gives damp areas particular attention, because bathrooms, laundries and outdoor spots are where a fitting wrong for its location turns up most often.

Baths, showers and other fixed water containers

Comparing the two editions, eCertify found three real changes in what counts as a wet location and where its zones run.

Clause 6.2.1, Scope. A deluge shower must now be treated as a shower and a self-contained eyewash as a fixed water container, where 2007 only offered this as an option in a note, and containers nobody normally puts any part of their body into now fall outside the clause.

Clause 6.2.2.1, Baths and showers. A shower with its plumbing connection in the ceiling gets its own Zone 1 rule, measured horizontally from the connection at 1.2 m in New Zealand (0.6 m applies in Australia only), and a barrier of at least 1.8 m may reduce it, whereas 2007 used one 1.2 m radius for every shower connection and, to reduce it, a barrier as high as the connection where that was above 1.8 m, the rule 2018 keeps for wall connections.

Clause 6.2.2.2, Other fixed water containers. The smaller Zone 2 for a container with fixed outlets now applies only up to 40 L per container instead of 45 L, so a bowl between 40 L and 45 L takes the larger zone.

Zone drawings for showers and sinks

By eCertify's count, six marked drawings either show a shower layout 2007 did not draw or carry the new 40 L limit.

Figure 6.5, Ceiling rose shower, plan. New: a plan view of a shower with its plumbing connection in the ceiling and no barrier, drawn with the 1.2 m New Zealand Zone 1, and a note that barriers and enclosures limit the zones as they do for a wall connection.

Figure 6.6, Ceiling rose shower, elevation. New: the same ceiling-connection shower seen from the side, with the New Zealand radius and heights marked.

Figure 6.8, Shower with hinged door. New: a plan view of an enclosed shower with a hinged door, a door being one of the barrier examples clause 6.2.2.1 now names.

Figure 6.11, Shower behind a barrier, elevation. Formerly Figure 6.8, this side view now covers a ceiling plumbing connection as well as a wall one, and Amendment 1 replaced the drawing, which marks the barrier at 1.8 m or more and Zone 1 at no more than 1.2 m.

Figure 6.13, Sinks with fixed outlets. Formerly Figure 6.10, the drawing for containers with fixed outlets now carries the 40 L limit in place of 45 L.

Figure 6.14, Flexible outlets and larger containers. Formerly Figure 6.11, the drawing for a flexible outlet or a bigger container now uses 40 L as its threshold too.

Equipment in bathroom zones

eCertify found three marked items on what may go in a bathroom zone, one of them from Amendment 2. General rules for socket-outlets, luminaires and other equipment are on Section 4, electrical equipment.

Clause 6.2.4.1, Degree of protection required. Amendment 2 rewrote the clause and deleted the table footnote calling for IPX5 in communal baths and showers, so Zones 1 and 2 need IPX4 and Zone 3 no set rating whether the bathroom is communal or not, where 2007 asked for IPX5 in Zones 1 to 3 of a communal one.

Clause 6.2.4.7, Electricity generation systems. New: generator sets, stand-alone power systems, grid-connected inverters and batteries may not go in any bathroom zone, a rule with no 2007 equivalent.

Table 6.1, Bathroom equipment by zone. No longer titled as guidance, the table gains a row keeping generation systems out of every zone and lost its communal IPX5 footnote to Amendment 2, while Amendment 1 only added a connecting word.

Swimming pools and spa pools

eCertify's read of the six pool and spa items: a bigger spa now counts as a bathroom, Zone 0 lights face tighter rules, and two kinds of equipment are kept out of the zones. Pool bonding, including a conductive pool shell that now needs bonding in its own right, is on Section 5, earthing and bonding.

Clause 6.3.2.2.1, Spa pools or tubs, general. A spa pool or tub holding up to 680 L, rather than 500 L, now follows the bathroom rules in clause 6.2, and the two-zone spa rules start above 680 L to match.

Clause 6.3.4.5.1, Pool equipment, general. Amendment 1 replaced the pool equipment clause with five subclauses, and this opening one now also asks that appliances and other equipment in Zone 0 meet clause 1.7.3 on equipment selection.

Clause 6.3.4.5.2, Zone 0 luminaires. Lights in Zone 0 of a pool must now comply with AS/NZS 60598.1 and AS/NZS 60598.2.18 and run on SELV only, at 12 V a.c. or 30 V ripple-free d.c., still without a protective earth, where 2007 also allowed PELV and applied its individual-source rule to lights as well as appliances.

Clause 6.3.4.7, Electricity generation systems. New: no generator set, stand-alone system, grid-connected inverter or battery may be installed in any pool or spa zone, where 2007's pool equipment rules stopped at switchboards.

Clause 6.3.4.8, Electricity distributor's electrical equipment. New: a pool or spa must not be sited where a pit, cabinet or other equipment owned by the lines company ends up inside one of its zones.

Table 6.2, Pool and spa equipment by zone. No longer titled as guidance, the pool table gains rows keeping generation systems and distributor equipment out of every zone, and Amendment 1 re-lettered and joined up its Zone 1 and Zone 2 entries without changing what they allow.

Fountains and water features

eCertify found five marked fountain items, and most of them carry the new pool rules across.

Clause 6.4.4.5.1, Fountain equipment, general. Amendment 1 rebuilt the fountain equipment clause on the pattern of the pool one, and appliances and other equipment in Zone 0 must now also meet clause 1.7.3 on equipment selection.

Clause 6.4.4.5.2, Zone 0 luminaires. Lights in Zone 0 of a fountain or water feature must now comply with AS/NZS 60598.1 and AS/NZS 60598.2.18 and run on SELV only, still unearthed, where 2007 also allowed PELV.

Clause 6.4.4.7, Electricity generation systems. New: generation systems of every kind, batteries and grid-connected inverters included, are kept out of both fountain zones.

Clause 6.4.4.8, Electricity distributor's electrical equipment. New: a fountain or water feature must not be placed where distributor-owned equipment, such as a connection pit or cabinet, would fall inside a zone.

Table 6.3, Fountain equipment by zone. New in 2018: a zone-by-zone selection table for fountains and water features, which 2007 lacked, and clause 6.4.4.1 now points to it.

In short

This page lists 23 of 36 marked changes in Section 6 of AS/NZS 3000:2018. Against 2007, eCertify sees the weight in five places: deluge showers and ceiling roses now have firm zone rules, the sink limit drops to 40 L and the spa limit rises to 680 L, communal bathrooms lose the IPX5 step, generation systems and distributor equipment stay out of every zone, and Zone 0 lights must be SELV to the luminaire standard. Five of the 23 are amendment edits only. Saunas, refrigeration rooms and hosed-down areas carry no change of substance, and none of the 23 is altered for New Zealand.