AS/NZS 3000:2018 clause 2.9.7, a New Zealand-only clause, makes arc fault detection devices (AFDDs) mandatory on some 20 A or smaller final subcircuits. Separately, the ban on switching a PEN (combined protective-earth-and-neutral) or earthing conductor was lifted for 11 months and is now back in force, unmodified, from 2 October 2026.

Part of eCertify's wider post on the AS/NZS 3000:2007-to-2018 transition, this one covers two code-compliance calls that come up directly on the jobs eCertify inspects: whether a circuit needs an AFDD, and whether a changeover switch is allowed to switch the PEN conductor.
Direct answer: AS/NZS 3000:2018 clause 2.9.7, a New Zealand-only clause, makes arc fault detection devices (AFDDs) mandatory on some 20 A or smaller final subcircuits. Separately, the ban on switching a PEN (combined protective-earth-and-neutral) or earthing conductor was lifted for 11 months and is now back in force, unmodified, from 2 October 2026.
Have mains or solar work that needs inspecting? Book a Record of Inspection with eCertify, or call 09 302 0884.
An AFDD is a device that disconnects a circuit when it detects an arc fault, the kind of sparking that happens inside damaged cable insulation or a loose connection, before it can start a fire. AS/NZS 3000 clause 1.4.14 defines it in exactly those terms.
Clause 2.9.7 is a New Zealand-only addition with no equivalent in the 2007 edition. It requires an AFDD on every final subcircuit rated 20 A or less supplying:
Outside those four categories, AFDDs are not mandatory under this clause, though the standard notes they may still be used to supplement protection on aged wiring.
AFDDs are still new in New Zealand, and eCertify has not dealt with many yet. On the jobs eCertify has worked on where clause 2.9.7 required one, the AFDDs have not nuisance tripped so far.
No. The mandatory rule in clause 2.9.7 only applies to the four location types above, each on a final subcircuit of 20 A or less. A general household power or lighting circuit outside those categories does not trigger the requirement on its own.
eCertify inspects and certifies this work rather than pricing or supplying the devices, so a figure here would be a guess. If an AFDD is required on your job, get a cost from the electrician doing the installation; it is a straightforward swap at the originating switchboard, same footprint as a standard circuit breaker, wired in the same way.
Clause 2.3.2.1.2(b) and (c) of AS/NZS 3000 bans two things: switching a neutral conductor on consumer mains, and switching a conductor used as a combined protective-earth-and-neutral (PEN) conductor; part (c) separately bans switching or isolating any earthing conductor. From 13 November 2025, a New Zealand modification, recommended by WorkSafe, disapplied that ban; WorkSafe's reasons, and why it was reversed, are covered below.
That modification has now been revoked. The Electricity (Safety) Amendment Regulations 2026 (SL 2026/309) came into force on 2 October 2026 and removed the disapplication, so the printed clause is back in force, unmodified, from that date: no switching a neutral, PEN or earthing conductor. Work installed or under way before 2 October 2026 does not have to be undone because the ban is back, but only if it is not electrically unsafe and complied with the rules as they stood immediately before 2 October 2026, and still does. Clause 8.3.7.2(b) was never modified, so testing still had to show that no switch or protective device operates in an earthing or PEN conductor. Whether a PEN switch fitted in that window ever complied is therefore open to argument: assess one found on site rather than pass it on sight.
Yes, but from 2 October 2026 the changeover arrangement cannot switch the PEN conductor, the neutral of consumer mains, or an earthing conductor. A changeover arrangement wired before 2 October 2026 does not need to be changed because the ban is back, provided it is not electrically unsafe and complied with the rules in force at the time. One that never switched the PEN is unaffected; if you are unsure what was fitted, have it inspected. New work from 2 October 2026 has to be designed around the restored ban.
WorkSafe recommended the change to MBIE and, in replies to Official Information Act requests, said it was a preparatory step towards two future uses: open-PEN detection devices on EV chargers, which cut the charger off from the installation earth if the supply neutral breaks so the car body cannot go live, and island-mode backup from solar, batteries or a generator while the grid is down. The NZ Electrical Inspectors Association, Master Electricians and Engineering New Zealand, later joined by the Solar Association, objected, warning that opening the PEN can leave every earthed metal part in a house, from taps to the hot water cylinder, live at up to mains voltage even when nothing else is wrong with the installation; the inspectors added that an RCD would not help. RNZ reported the dispute from December 2025. MBIE said there "remains significant concern within the sector about whether it can be used safely", noted that PEN switching had seen "little to no uptake", and restored the ban, in its own words, "to remove the risk of potential significant harm while further work is undertaken." For new work, the practical position is the same as it was under the 2007 edition: the printed clause never allowed switching those conductors, and from 2 October 2026 it does not allow it again.
AFDDs and PEN switching are both New Zealand-specific features of the citation that moved to AS/NZS 3000:2018 on 13 November 2025, alongside the RCD changes covered in eCertify's other spoke post. The same transition rules apply here as to the rest of the standard: an installation that already complied with the pre-13-November-2025 rules is not made non-compliant by the edition change, and a changeover arrangement installed before 2 October 2026 can stay only if it is not electrically unsafe and complied with the rules at the time. The full detail on the transition and the 12 November 2026 deadline is in eCertify's main post on the AS/NZS 3000 2007-to-2018 change.
Whether an AFDD was fitted where required, and whether a changeover switch complies with the current PEN rule, are exactly the kind of findings that come up on a Mains Work ROI inspection. eCertify's Mains Work ROI service (NZ$349.90 including GST) covers that inspection and the Record of Inspection it produces; more on what counts as high-risk work is in eCertify's write-up of high-risk electrical work and mains inspections.
AS/NZS 3000:2018 clause 2.9.7 makes AFDDs mandatory in New Zealand on 20 A or smaller final subcircuits in four specific location types, a rule with no equivalent in the 2007 edition. The ban on switching a PEN, neutral or earthing conductor, lifted for backup and changeover arrangements from 13 November 2025, is back in force unmodified from 2 October 2026 under the Electricity (Safety) Amendment Regulations 2026 (SL 2026/309); existing arrangements can stay only where they are not electrically unsafe and complied at the time. eCertify, Auckland's electrical compliance specialist, checks both on a Mains Work ROI inspection, because each is an easy thing to get wrong on paperwork or design during a transition with this many moving dates.
Need high-risk work inspected? See eCertify's Record of Inspection page for Auckland electricians for prices and booking, or call 09 302 0884.
On final subcircuits of 20 A or less supplying points in fire-risk material stores, locations with irreplaceable items, flammable historic buildings, or school dormitory socket circuits. Those are the four categories clause 2.9.7 names.
Anywhere outside those four categories. A standard household circuit with none of those features does not trigger the mandatory AFDD rule.
No, not from 2 October 2026. The ban on switching a PEN, neutral or earthing conductor is back in force under the Electricity (Safety) Amendment Regulations 2026 (SL 2026/309).
A conductor that combines the neutral and protective earth functions in a single wire, used in some New Zealand earthing arrangements.
Not because the ban is back. It can stay, provided it is not electrically unsafe and complied with the rules in force when it was installed. If you are unsure whether it switches the PEN or an earthing conductor, have it inspected.