An eCertify inspector at the outdoor meter box of an Auckland house
Mains and solar inspections for Auckland electricians

Record of Inspection (ROI) for electricians in Auckland

Done mains work or a solar install and need it inspected? eCertify, an Auckland electrical certification and inspection company, inspects mains work and solar PV for electricians across the Auckland region and issues the Record of Inspection (ROI). An ROI is the independent inspector's signed record of whether high-risk electrical work complies with the Electricity (Safety) Regulations 2010 and is electrically safe.

Regulation 70 of those regulations requires high-risk work to be inspected, and regulation 65(4) says the job is not complete until your certificate of compliance (COC) and the ROI are both issued. eCertify attends mains work and parallel generation, including solar PV and battery or generator systems.

eCertify's fixed prices are NZ$349.90 including GST for a mains work inspection and NZ$449.90 including GST for a solar PV inspection up to 10 kW. eCertify puts the ROI in your hands within 48 hours of the inspection and lodges the job on Energy Safety's High Risk Database. Auckland region only.

Last reviewed by Jordan Statham, registered electrical inspector (EW129010), 11 October 2026

Or call 09 302 0884

Where can I get a mains work or solar inspection in Auckland?

You can get a mains work or solar inspection in Auckland from eCertify, which inspects high-risk electrical work for electricians across the Auckland region, with callout and mileage inside the fixed price.

eCertify attends two of the high-risk categories in regulation 6A(2) of the Electricity (Safety) Regulations 2010: mains work, and parallel generation, including solar PV and battery or generator systems. The regulation also lists high voltage, hazardous areas, installations for electrical medical devices and others. Those are specialist fields and eCertify does not attend them.

What eCertify gives Auckland sparkies on top of the inspection:

  • Free advice before you start, on the rules and what the inspector will want to see.
  • The full pre-inspection checklist when you book.
  • The ROI in your hands within 48 hours of the inspection, database lodgement done for you.
  • Urgent inspections fitted in where eCertify can, so call even if you forgot to book ahead.
eCertify inspector holding a test instrument for a mains work inspection in Auckland

What are the requirements to complete an electrical ROI in NZ?

An electrical ROI in NZ can only be completed by an inspector authorised to inspect high-risk prescribed electrical work who did not do, supervise or certify that work. The Electricity (Safety) Regulations 2010 set four requirements:

  • Who. Regulation 71(1) requires the inspector to be authorised to inspect high-risk work. Regulation 71(2) rules out anyone who carried out the work, supervised it, or issued its COC.
  • The inspection. Regulation 70(3) requires whatever tests and visual checks it takes to be satisfied the work complies and the installation is, and will be when livened, electrically safe. It sets an outcome, not a checklist.
  • The record. Regulation 72(2) requires the ROI to identify the work, be signed and dated by the inspector, carry the authentication mark (regulation 111B), and state whether the work complies and the installation is electrically safe. Your COC is attached (regulation 72(3)).
  • Afterwards. The inspector lodges the job on the High Risk Database (regulation 74F(1)) and keeps a copy of the ROI for at least seven years (regulation 72A(1)(b)).

eCertify's director, Jordan Statham, is an EWRB-registered electrical inspector (EW129010, Electrical Inspector class), registered since 2017. The Electrical Workers Registration Board's public register shows every practitioner's class, so you can check any inspector before you book, Jordan included.

What work needs an ROI?

High-risk prescribed electrical work on a low or extra-low voltage installation needs an ROI: regulation 70(1) requires the work to be inspected, and regulation 72(1) requires a written record of that inspection. eCertify inspects two kinds of it.

Mains work. Regulation 4 defines it as work on the mains (the fittings that supply the MEN switchboard closest to the point of supply), on the main earthing system, or on the MEN link in that switchboard. New consumer mains, a new main earth or electrode, and terminating the mains at a new MEN switchboard all count.

Solar PV and parallel generation. Regulation 6A(2) lists photovoltaic systems and mains parallel generation systems as separate high-risk items. Regulation 60(2) adds the standards: AS/NZS 5033 for a PV array, and AS/NZS 3010 and AS/NZS 4777.1, as applicable, for low voltage parallel generation connected to the national grid. eCertify inspects grid-tied solar PV and battery or generator systems.

Switchboard swaps are where the arguments start. eCertify's guide to high-risk electrical work and mains inspections works through them, with the full regulation 6A list.

How much does an ROI inspection cost?

eCertify charges NZ$349.90 including GST for a mains work inspection and ROI, and NZ$449.90 including GST for a solar PV inspection and ROI on a standard residential or light commercial system up to 10 kW.

Inspection and ROIeCertify price, including GSTHow to book
Mains work (consumer mains, main earth, MEN link)NZ$349.90Book online
Solar PV up to 10 kW, standard residential or light commercialNZ$449.90Enquire or call 09 302 0884
Mains work and solar PV up to 10 kW on the same visitNZ$449.90Enquire or call 09 302 0884
Solar PV above 10 kWQuoted before bookingEnquire
Battery or generator system, no PVQuoted before bookingEnquire

Each eCertify price is the total: callout and mileage anywhere in Auckland, the inspection and testing, the ROI and the High Risk Database lodgement. The solar inspection is not in eCertify's online store yet, so book it through the form below or by phone. Mains work and solar PV up to 10 kW on the same job is one eCertify inspection at NZ$449.90 including GST, not two.

Re-inspection is extra. If eCertify has to come back for something that should have been ready on the day, a re-inspection charge applies. eCertify's full price list is on its electrical inspection cost page.

ROI, COC and ESC: how do they fit together?

High-risk work ends with three documents from two people. On an eCertify job, you issue the COC and the ESC, and eCertify issues the ROI.

  • Certificate of compliance (COC). From the electrician who did the work. Regulation 65(1) requires one for all general and high-risk work, and regulation 66(1) has the manufacturer's instructions and supplier declarations of conformity you used attached to it.
  • Record of Inspection (ROI). From the independent inspector, with your COC attached (regulation 72(3)).
  • Electrical safety certificate (ESC). From the person who completed the work, once satisfied the installation is safe to use (regulation 74A(1)), and as soon as practicable after connection (regulation 74C).

Regulation 65(4) ties them together: high-risk work is not complete until the COC and the ROI are both issued. Insurers and councils often call the whole family "energy works certificates". That is the everyday umbrella name, not a legal one, and eCertify's guide to electrical certificates sets them side by side.

What to have ready before the inspector arrives

eCertify asks for the items below on site before the inspector arrives. A missing item that forces a second visit is charged as a re-inspection.

Mains work:

  • The main earthing conductor tagged or identified at the switchboard end.
  • The main earth labelled at the electrode, with the warning AS/NZS 3000 clause 5.5.1.3 requires.
  • The main earth clamped firmly to the electrode, not loose. AS/NZS 3000 clause 5.5.1.2 requires a connection that conducts properly and is protected against corrosion, so check an existing earth for corrosion if you are keeping it with new mains.
  • The electrode location written legibly at the switchboard, as AS/NZS 3000 clause 5.3.6.4 requires, and the electrode connection accessible for inspection and testing.
  • Main earthing conductor resistance tested. AS/NZS 3000 clause 5.5.1.4 caps it at 0.5 ohm.
  • Mains polarity tested against an independent earth, and earth fault-loop impedance tested. AS/NZS 3000 clause 8.3.3.1 makes both mandatory tests.
  • The MEN link fitted in the main switchboard. Under the MEN system, AS/NZS 3000 clause 5.1.3 has the supply neutral earthed at every installation.
  • Pole fillers in every empty space on the switchboard. AS/NZS 3000 clause 1.5.4.4 requires live parts to sit inside an enclosure or behind a barrier.
  • Any meterboard switch fully enclosed.
  • Your COC on site, and your ESC if you have issued it.
  • Access arranged, including any locked board space.

Solar PV and parallel generation:

  • Your inspection and test results. AS/NZS 5033 clause 4.7.1 requires a PV array to be inspected and tested before it goes into service, and clause 4.7.3.1 adds the AS/NZS 3000 mandatory tests.
  • Your COC, with the inverter and battery manufacturer's instructions and supplier declarations of conformity attached or referenced (regulation 66(1) and 66(3)).
  • Access to the full DC cable run, so eCertify can sight all of it and confirm the run is correct and compliant.
  • The system documentation on site. AS/NZS 5033 clause 6.1 requires it at completion, and clause 6.2 sets out what the system manual holds: system and component ratings and the commissioning date, the equipment list with models and serial numbers, the shutdown and isolation procedure, a connection diagram with the array's ratings, where the disconnection devices are and how the cables run, the commissioning records and installation checklist, and the manufacturers' documentation for the equipment. eCertify expects a full dossier on every solar job, and more is better than less.

eCertify sends the full pre-inspection checklist when you book.

What electricians most often forget, in eCertify's experience, are small things: the electrode location sticker on the switchboard, pole fillers in the board, and a loose clamp on the main earth. Now and then the MEN link is missing altogether. Jordan Statham, eCertify's director, puts that at "maybe 10% of cases". The switchboard sticker is a quick fix, and eCertify has the electrician put it right while it is on site.

eCertify tests mains polarity against an independent earth on every job, and one mains job shows why. The overhead service cables had not been sleeved or identified (AS/NZS 3000 clause 3.8.1 requires every conductor to be clearly identified), and they had been terminated into the new point of entry crossed: phase in the neutral terminal, neutral in the phase terminal. The network had already livened the service at the street, but the main switch had not been turned on. eCertify's polarity test found the crossed mains, the pole fuse was pulled, and the conductors were swapped at the point of entry, where the service line was colour-coded, before the installation was put back into service.

Polarity testing matters because a crossed connection can kill. In 2010 an Auckland homeowner died after the phase and neutral were swapped at his new mains connection, which made the earthed metalwork in the house live. The Electrical Workers Registration Board found that the electrician did no testing, and that the inspector did not carry out the tests that would have caught the swap. That is why eCertify never skips the polarity test.

How fast do I get the ROI, and does eCertify lodge it on the High Risk Database?

eCertify puts the ROI in your hands within 48 hours of the inspection, and eCertify lodges the job on Energy Safety's High Risk Database for you. Regulation 74F(1) makes lodging the inspector's job, not the electrician's.

eCertify keeps a copy of every ROI for at least seven years, as regulation 72A(1)(b) requires, so if a customer asks you for it in year five, eCertify can produce it.

In a hurry? If a livening or a customer is waiting on you, say so when you book. eCertify can often fit in an urgent inspection, depending on the day's bookings.

The regulations set their own outer limits as well. An inspector has 20 working days after issuing an ROI to give a copy to the person who contracted for the work (regulation 72A(1)(a)), and 20 working days after its date to lodge it (regulation 74F(1)). Those are legal limits, not eCertify's service standard.

eCertify inspector completing the paperwork after inspecting high-risk electrical work in Auckland

Frequently asked questions

What does ROI stand for in electrical work?

In New Zealand electrical work, ROI stands for Record of Inspection: the written record an inspector prepares after inspecting high-risk prescribed electrical work, as regulation 72 of the Electricity (Safety) Regulations 2010 requires. eCertify issues ROIs for mains work and solar PV across Auckland.

Who is not allowed to inspect my work?

Regulation 71(2) of the Electricity (Safety) Regulations 2010 bars anyone who carried out the work, supervised someone carrying it out, or issued its COC. That rules out you, anyone who worked on the job with you, and whoever supervised you on it. eCertify checks all three roles before accepting a booking, and an eCertify inspector who held any of them declines the job.

What happens if the work does not pass?

eCertify gives you a written list of what needs fixing, each item tied to the regulation or standard it does not meet. A finding eCertify cannot cite is not a finding. What eCertify finds is mostly small: on mains work, a loose earth clamp, a missing electrode location sticker or a missing MEN link; on solar PV, the wrong conduit, missing or mixed-up labels, or DC cable left exposed or lying on the roof. Where it can, eCertify has the electrician put these right on site before it passes the job. Fix the items and eCertify re-inspects, for a re-inspection charge. If the work presents an immediate danger, regulation 19 of the Electricity (Safety) Regulations 2010 requires the inspector to tell the owner or occupier and WorkSafe. eCertify isolates the affected part with the owner's permission first, then reports.

Does eCertify do meter work?

No. eCertify is not a metering equipment provider (MEP) and does not install, relocate, re-seal or inspect energy meters. Metering work goes through the property's energy retailer or its metering equipment provider, and is inspected by a network warranted electrical inspector. Tell eCertify if metering is in scope and the office will point you to one in your area.

In short

eCertify inspects mains work and parallel generation, including solar PV and battery or generator systems, for electricians across Auckland, and issues the Record of Inspection that regulation 65(4) says high-risk work needs before it is complete. eCertify's fixed prices are NZ$349.90 including GST for mains work and NZ$449.90 including GST for solar PV up to 10 kW, and larger solar and battery or generator systems are quoted. eCertify puts the ROI in your hands within 48 hours of the inspection and lodges the job on the High Risk Database. The inspector is independent of your work, as regulation 71(2) requires, and eCertify is not a metering equipment provider.

Get your mains or solar job inspected

Book mains work online in a few minutes, or tell eCertify about your solar, battery or generator job below. The office confirms the price, including GST, before anything is booked. Auckland region only.

Book an inspection

We will tell you which certificate you need.

eCertify covers the Auckland region. If your property is outside Auckland, we are not able to help.