High Risk Mains Work - Electrical Inspection
Including ROI certification compiling and High Risk Database (Energy Safety) submission
Applies for mains work only.
METERS
eCertify are not MEPS (metering equipment providers)
We do not install new meters, relocate existing meters or re-seal meters.
Metering work must be carried out by a network approved inspector
Feel free to call us if you’d like recommendations for network approved inspectors in your area.
PRE-INSPECTION NOTES FOR THE ELECTRICIAN
Pre-Inspection, please ensure
Main earthing conductor is identified at the DB end of main earth conductor (tag or label)
Main earth electrode location listed on switchboard
Correctly clamped (not loose) main earth electrode with tag
Tested main earth continuity (must be less than 0.5ohm)
Tested mains polarity with independent earth
Tested earth fault loop impedance
Earth electrode is located and accessible
Fully enclosed meterboard switch (if applicable)
ESC/COC on site and ready.
IMPORTANT
Please be aware that re-inspection charges will apply if items are missed and we need to return to site.
Also additional time may be charged if we need to wait while issues are rectified at the time of inspection.
If you have any queries about the way in which we need work to be completed, please reach out ahead of the inspection for confirmation.